In band, 11.00 kV
Grid
Specification
- Size
- 600 × 500 × 1700 mm, 1800 on castors
- Rack
- 19″, 20U
- AVR
- 2 × Huaming HMIET-I, master and follower
- Tap indicator
- 2 × Huaming HMC-3C
- Test units
- Grid source, tap‑changer simulator
- Screen
- 22″ on a stand, keyboard tray
- Supply
- 230 V, one 13 A plug
- Castors
- 3″, lockable
What it is for
- Show the whole AVR system working, live
- Demo parallel control: master and follower
- Something real to show at office visits
- One reusable asset for shows and training
- Test AVR settings in Singapore before site
Dots: how clearly the sketch shows it.
Build
Rack layout
| Slot | Size | Height, mm | Unit |
|---|---|---|---|
| U20 | 1U | 1117–1159 | Cable entry, brush strip |
| S5, S6 | 3U | 984–1115 | 2 × HMC-3C tap indicator |
| S4 | 4U | 806–981 | HMIET-I AVR, T2 follower |
| S3 | 4U | 628–803 | HMIET-I AVR, T1 master |
| S2 | 4U | 450–625 | Tap‑changer simulator |
| S1 | 4U | 272–447 | Grid source |
| Locker | 120–255 | Cable drawer |
Before building
- Lower the tray to 1.0–1.1 m
- Heaviest unit at the bottom
- Leave 100 mm behind each unit
- Fan low, louvres high
- RCD and earth stud on the frame
Swipe for the side view